Temporary Installations
Article 590: Time Limits, Wiring Methods, GFCI and the Assured Grounding Program
NFPA 70 National Electrical Code, 2023 edition · Reviewed 2026-09-21
"Temporary Wiring" is a named bullet under Services, Service Equipment & SDS in the Florida DBPR blueprint. Article 590 is short and almost every item is a number (90 days, 150 V, 10 ft, 3 months, 600 V, 10,000 A) or a which-receptacles-get-GFCI rule. Written from the 2023 text (the Florida edition; 2023 section numbers throughout — 590.1 scope, 590.2 all wiring installations, 590.3 time constraints, 590.4 general, 590.5 listing of decorative lighting, 590.6 GFCI, 590.7 guarding, 590.8 overcurrent devices).
1. What still applies — 590.2
- 590.2(A): except as specifically modified by Article 590, all other requirements of the Code for permanent wiring apply to temporary installations.
- 590.2(B): temporary wiring methods are acceptable only if approved based on the conditions of use and any special requirements of the temporary installation.